Common Problems and Solutions of Diesel Generator Sets
2023-04-09 18:10:10
Common Faults, Causes and Solutions of Diesel Generator Sets
I. Failure to Start
-
Insufficient battery voltage, oxidized and loose wiring terminals, weak starting motor.Solution: Clean the terminals, charge or replace the storage battery.
-
Air trapped in fuel pipeline, water contained in diesel fuel, excessive accumulated water in water-oil separator, resulting in fuel supply interruption.Solution: Drain accumulated water, bleed air from fuel pipeline, replace diesel filter.
-
Severe blockage of air filter, insufficient air intake.Solution: Blow clean or replace the air cleaner.
II. Unstable Generator Voltage with Fluctuating Readings
- Damaged or unstable AVR (Automatic Voltage Regulator); worn carbon brushes causing poor contact.
- Fluctuating load and loose circuit wiring terminals.
- Fluctuating engine rotating speed.
Solutions: Replace carbon brushes, overhaul voltage regulator, fasten wiring terminals, and avoid frequent startup & shutdown of high-power equipment.
III. Abnormal Exhaust Smoke
-
Black smoke: Overloaded unit, clogged air filter, poor atomization of fuel injectors.Solution: Reduce electrical load, clean air filter, calibrate fuel injectors.
-
Blue smoke: Engine oil enters cylinders for combustion, excessive engine oil level or worn piston rings.Solution: Drain excess engine oil and carry out major engine overhaul.
-
White smoke: Water mixed in diesel fuel, excessively low water temperature or water seepage from cylinder head gasket.Solution: Replace with qualified diesel fuel, fully preheat the unit, and inspect cylinder head gasket.
IV. Excessively High Water Temperature & High Temperature Alarm
- Radiator blocked by dust, catkins and debris, leading to poor heat dissipation.
- Insufficient coolant/antifreeze or faulty thermostat.
- Long-term overloaded operation.
Solution: Clean the water tank, replenish antifreeze; prohibit continuous full-load operation.
V. Low Engine Oil Pressure Alarm
- Insufficient engine oil volume, deteriorated engine oil that has not been replaced for a long time.
- Clogged oil filter or insufficient pressure output from oil pump.
Solution: Top up or replace engine oil, replace oil filter.
VI. Excessive Vibration & Loud Noise During Operation
- Aged and damaged vibration-damping rubber pads at the base.
- Loose anchor bolts and unbalanced stress on four engine support feet.
- Excessive coaxiality deviation between alternator and diesel engine.
Solution: Replace vibration-damping pads and fasten base bolts.
VII. Automatic Shutdown (Engine Stalls Mid-operation)
- Depleted fuel or blocked fuel pipeline.
- Activation of over-temperature / low oil pressure protection, triggering automatic shutdown via controller.
- Malfunction of sensors.
Solution: Inspect fuel pipeline, troubleshoot high water temperature and low oil pressure issues, and overhaul the control module.
VIII. Electric Leakage & Circuit Breaker Tripping Power Cut
- Damp wiring, aged and damaged cables; damp alternator winding coils.
- Short circuit or overload of electrical equipment.
Solution: Take moisture-proof treatment, inspect external loads, and never operate under overload conditions.