How to maintain a diesel generator?
2023-11-12 08:15:17
Maintenance Methods for Diesel Generators
I. Pre-start Inspection (Before Every Use)
1. Engine Oil Inspection
- After shutting down and standing for 5每10 minutes, pull out the oil dipstick. Maintain the oil level midway between the upper and lower scale marks.
- Replace the oil immediately if it turns black, becomes thin, or contains impurities.
- Change engine oil every 250每300 operating hours. Use -10# or -20# antifreeze engine oil in winter.
2. Coolant (Antifreeze) Inspection
- Keep the water tank liquid level at the marked line. Top up with antifreeze of the same model when low; never add tap water directly.
- Prevent overheating and boiling in summer; drain all cooling water after shutdown in winter to avoid cylinder block cracking from freezing.
3. Fuel System
- Use qualified national standard diesel. Regularly drain accumulated water and sediment from the bottom of the fuel tank and diesel filter.
- Check fuel pipes for damage and oil leakage; fasten all pipe joints and bleed air fully to avoid unexpected shutdown due to fuel supply interruption.
4. Battery Inspection
- Voltage standard: 24V units shall maintain 24每27V; 12V units shall stay above 12.5V.
- Check terminal posts for looseness, oxidation or white powder; fasten terminals regularly and clean terminal connectors.
- For long-term idle storage, charge the battery every 15 days to avoid damage from power depletion.
5. Appearance & Earthing Inspection
- The main earthing cable of the complete unit must be firmly connected to prevent electric leakage.
- Clear dust, catkins and debris from fans and heat sinks; inspect exhaust ducts of silent-type units for unobstructed ventilation.
II. In-operation Maintenance (While Running)
- Monitor dashboard readings: engine oil pressure, coolant temperature, voltage and frequency. Normal coolant temperature ranges from 75⊥ to 90⊥; standard engine oil pressure is 0.25每0.4 MPa.
- Strictly prohibit long-term overloaded operation. The optimal load range is 70%每80% of rated power to extend unit service life.
- Do not start or stop the unit with sudden full load; increase and decrease load gradually.
- Listen and observe for abnormal noises or exhaust smoke during operation:
- Black smoke: Excessive load or clogged air filter
- Blue smoke: Engine oil burning inside cylinders
- White smoke: Water contained in diesel fuel or cylinder block faults
- Ensure good ventilation in the generator room. For fully enclosed rooms, guarantee smooth air intake and exhaust.
III. Periodic Scheduled Maintenance (By Operating Hours)
1. 50-Hour Maintenance (Short-term Routine Service)
- Clean the air filter. In dusty environments, blow compressed air from inside out. Replace the air filter directly if severely clogged.
- Inspect battery wiring and belt tension (generator drive belt).
- Drain accumulated water and impurities from diesel filters and water-oil separators.
2. 250每300-Hour Maintenance (Primary Maintenance)
- Replace engine oil and oil filter.
- Replace diesel filter and water-oil separator element.
- Thoroughly clean the air filter; install a brand-new filter under harsh working conditions.
- Tighten all bolts on the complete unit; inspect oil pipes and water pipes for leakage.
3. 500-Hour Maintenance (Secondary Maintenance)
- Complete all service items of Primary Maintenance.
- Replace antifreeze; clear dust from the exterior of the water tank and clean the radiator.
- Inspect carbon brushes and slip rings of the alternator, remove dust deposits, and replace carbon brushes with excessive wear.
- Calibrate the Automatic Voltage Regulator (AVR) and check all wire connectors.
4. 1000-Hour Major Overhaul (Comprehensive Deep Maintenance)
- Replace all filter elements, engine oil and antifreeze.
- Test and calibrate fuel injectors and high-pressure fuel pumps.
- Inspect and adjust valve clearance.
- Remove dust from stator and rotor, and test winding insulation performance.
- Check clutches and shock-absorbing pads for aging or cracking.
IV. Maintenance for Long-term Idle Storage (Export Standby Units & Stock Units)
- Run the unit under no load for 15每20 minutes to fully drain residual water from pipelines.
- Drain all engine oil, diesel fuel and cooling water.
- Remove the battery for separate storage and charge it once every month.
- Seal air intake and exhaust openings, cover the entire unit with a rainproof and dustproof cover, and store it in a dry and well-ventilated room.
- Start the unit once every 30 days and run it for 10每15 minutes.
V. Key Maintenance Points for the Alternator (Electrical Section, Excluding Diesel Engine)
- Prevent the unit from being soaked by rain; install rainproof covers for outdoor mobile power stations.
- Keep the interior of the alternator stator dry and free of water ingress or dampness; dry the windings thoroughly before operation if used in humid environments.
- Avoid long-term overload or short-circuit operation; short circuits can easily burn out the stator windings.
- Measure insulation resistance of windings once every year.
VI. Operation Prohibitions (For Overseas Customers)
- Never operate a cold unit under full load immediately; preheat the engine for 3每5 minutes first.
- Do not shut down the unit right after high-temperature operation; run it under no load for several minutes to cool down before shutdown.
- Only use lubricating oil, antifreeze and diesel fuel of specifications specified by the original manufacturer.